1. |
Verification using fingerprint, card and password |
|
1. |
Verify enrolled fingerprint at R2c. The Door Unlock LED will light up indicating
door open. |
2. |
Verify using password and card to unlock the door |
3. |
Verify invalid fingerprints at R2c. The Door Locked LED will light up indicating
door will not open for invalid verication. |
|
|
|
2. |
Door access security using door sensor and alarm |
|
Amend the settings under Doors to demonstrate functions of each option. Refer to
Configuring settings to doors at Chapter 2 Management of Device and Door |
|
|
1. |
Change the following and upload settings to Ingressus |
|
a. |
Lock Open Duration = 3s |
b. |
Door sensor Type = NC |
c. |
Door sensor delay = 1s |
|
2. |
Verify to unlock door, Door unlock LED will light up |
3. |
Switch door sensor to NO position to simulate door open |
4. |
Wait for 3s and Door Locked LED to light up |
5. |
Wait for 1s and Alarm shall be activated |
6. |
Switch door sensor to NC position to simulate door closing |
7. |
Alarm shall be de-activated |
8. |
Make sure Door Locked LED light up to simulate door close |
9. |
Switch door sensor to NO position to simulate door force open |
10. |
Alarm shall be activated immediately |
11. |
Switch door sensor to NC position to simulate door close |
12. |
Alarm shall be de-activated immediately |
|
|
|
3. |
Antipassback |
|
Amend settings under Zone, which is available in Ingressus Only to demonstrate
Antipassback feature. Refer to Chapter 3 Setup of Zones under Section Antipassback for details. |
|
|
1. |
Set the Antipassback between readers of Door 1 and readers of Door 2
respectively and upload it to Ingressus |
2. |
Verify at In device once followed by verication at Out device once to simulate
normal in-out operation |
3. |
Verify at In device once to simulate clocking in scenario |
4. |
Verify at In device again to simulate clocking in again |
5. |
Door Unlocked LED will not light up to indicate that the door will not be
opened when you set Antipassback on. |
6. |
Verify once at the Out device then followed by once at the In device. Door
unlocked LED will light up to indicate door open. |
|
|
|
4. |
Interlocking |
|
Amend settings under Zone, which is available in Ingressus Only to demonstrate
Interlocking feature. Refer to Chapter 3 Setup of Zones under Section Interlocking for details. |
|
|
1. |
Activate the option and upload to Ingressus |
2. |
Verify at In device, the Door Unlocked LED will light up |
3. |
Switch door sensor to NO position to simulate door open |
4. |
Verify at Out device to simulate user is going to open the second door |
5. |
Door Locked LED will light up indicating that door remains close |
6. |
Switch door sensor to NC position to simulate door close |
7. |
Verify again at Out device and Door Unlocked LED will light up to indicate door
open |
|
|
|
5. |
Fire alarm (smoke and heat sensor) |
|
Amend settings under Zone, which is available in Ingressus Only to demonstrate
Fire alarm feature. Refer to Chapter 3 Setup of Zones under Section Fire alarm for
details. |
|
|
1. |
Set Auxiliary Input Shorted under Trigger Condition |
2. |
Set Auxiliary Input 1 under Input Point Address |
3. |
Check Lock 1 and Lock 2 |
4. |
Select Normal Open under Action Type |
5. |
Upload settings to Ingressus |
6. |
Press the test button of the smoke and heat sensor to simulate fire or smoke
detected |
7. |
Door Unlocked LED of both doors will light up to indicate door open |
|
|
|
6. |
Burglar alarm (motion detector) |
|
Amend settings under Zone, which is available in Ingressus Only to demonstrate
burglar alarm. Refer to Chapter 3 Setup of Zones under Section Fire alarm for details. |
|
|
1. |
Set Auxiliary Input Disconnected under Trigger Condition |
2. |
Set Auxiliary Input 2 under Input Point Address |
3. |
Check Auxiliary 1 only |
4. |
Select Normal Open under Action Type |
5. |
Upload settings to Ingressus |
6. |
Wave in front of the motion detector to simulate movement |
7. |
Alarm should trigger immediately |
|